GE IC693ALG221J
GE IC693ALG221J是一款用于GE Fanuc自动化系统的模拟电流输入模块。它主要用于接收来自外部设备的4-20mA模拟电流信号,并将其转换为PLC可识别的数字信号。这种类型的模块在工业自动化中非常常见,用于测量各种物理量,如压力、温度、流量等。
产品参数
通道数:4通道
输入类型:模拟电流输入
输入范围:默认4-20mA,可通过跳线调整为0-20mA
分辨率:12位
采样率:每通道0.5毫秒
隔离:通道间隔离
安装方式:DIN导轨安装
产品规格
工作温度:0℃~55℃
相对湿度:5%~95%(无凝露)
系列
IC693ALG221J属于GE Fanuc Emerson的Series 90-30系列,该系列产品主要用于工业自动化系统的I/O扩展。
特征
高精度:12位分辨率,保证测量精度。
灵活配置:可通过跳线调整输入范围。
隔离设计:避免通道间干扰。
快速响应:每通道0.5毫秒的采样率,满足实时控制的需求。
易于安装:DIN导轨安装,方便快捷。
作用
接收外部4-20mA模拟电流信号。
将模拟电流信号转换为PLC可识别的数字信号。
扩展PLC的模拟输入点数。
用途
工业自动化系统
过程控制系统
数据采集系统
应用领域
制造业:用于测量压力、温度、流量等
石油化工:用于监测过程变量
能源:用于监测发电设备的运行状态
水处理:用于监测水质参数
英文说明
Product Overview
The GE IC693ALG221J is a 4-channel analog current input module for GE Fanuc automation systems.It is primarily used to receive 4-20mA analog current signals from external devices and convert them into digital signals that can be recognized by the PLC.This type of module is commonly used in industrial automation for measuring various physical quantities such as pressure,temperature,and flow rate.
Product Specifications
Number of channels:4 channels
Input type:Analog current input
Input range:4-20mA by default,adjustable to 0-20mA via jumper
Resolution:12-bit
Sampling rate:0.5 milliseconds per channel
Isolation:Channel-to-channel isolation
Mounting:DIN rail mounting
Product Features
High accuracy:12-bit resolution ensures accurate measurements.
Flexible configuration:Input range can be adjusted via jumper.
Isolation design:Prevents interference between channels.
Fast response:0.5 millisecond sampling rate per channel meets real-time control requirements.
Easy installation:DIN rail mounting for quick and easy installation.
Function
Receives external 4-20mA analog current signals.
Converts analog current signals into digital signals that can be recognized by the PLC.
Expands the number of analog input points of the PLC.
Applications
Industrial automation systems
Process control systems
Data acquisition systems
Industries
Manufacturing:Used to measure pressure,temperature,flow rate,etc.
Oil and gas:Used to monitor process variables
Energy:Used to monitor the operating status of power generation equipment
Water treatment:Used to monitor water quality parameters